Raystat-V5 Thermostat
Raychem RAYSTAT-V5 Heating Cable Controller
The Raychem RAYSTAT-V5 is an electronic controller designed for operation with Raychem self-regulating heating cables. It provides flexible temperature control for pipe freeze protection and temperature maintenance systems, helping to ensure reliable operation and improved energy efficiency.
Featuring line sensing and ambient sensing capabilities, the RAYSTAT-V5 can be configured to suit different heating applications. Its Proportional Ambient Sensing Control (PASC) algorithm adjusts heating operation according to ambient temperature conditions, helping to optimise energy consumption when operating in ambient sensing mode.
Efficient and Reliable Temperature Control
The RAYSTAT-V5 is designed for straightforward setup and programming, with the flexibility to configure the controller before final installation. Pipe temperature monitoring with high and low temperature alarms helps identify potential system issues, while the integrated alarm relay can signal power, temperature or communication problems.
Suitable for wall mounting in outdoor locations, the RAYSTAT-V5 offers a practical control solution for a range of Raychem heating cable applications.
Key Features and Benefits
Designed for operation with Raychem self-regulating heating cables
Suitable for pipe freeze protection and temperature maintenance systems
Flexible temperature control using line sensing and/or ambient sensing
Proportional Ambient Sensing Control (PASC) algorithm for enhanced energy savings in ambient sensing mode
Easy setup and programming
Pipe temperature monitoring with high and low temperature alarms
Alarm relay with changeover contact to signal power, temperature or communication problems
Can be configured before final installation
Wall-mountable design suitable for outdoor locations
Password protection for parameter settings
USB port for pre-configuration when power is off and firmware upgrades
Electrical Specifications
Supply voltage: 180–253 V AC, 50/60 Hz
Operating ambient temperature: -40°C to +40°C
Power consumption: Maximum 3.5 VA
Output relay switching capacity: 25 A at 230 V AC
Power supply terminal capacity: Maximum 3 × 6 mm²
Heating cable terminal capacity: Maximum 3 × 6 mm²
Alarm terminal capacity: Maximum 3 × 1.5 mm²
Pipe sensor terminal capacity: Maximum 2 × 1.5 mm²
Alarm Relay Specifications
Relay type: Single-pole double-throw (SPDT), volt-free contact
Maximum switching capacity for resistive loads: 1 A at 30 V DC or 0.5 A at 125 V AC
Maximum voltage: 60 V DC or 125 V AC
Applications
The Raychem RAYSTAT-V5 is designed for heating cable control in applications such as:
Pipe freeze protection
Water pipe frost protection
Temperature maintenance systems
Commercial and industrial pipework
Building services heating cable installations
The Raychem RAYSTAT-V5 offers a flexible and reliable solution for controlling self-regulating heating cables, combining straightforward programming, intelligent energy-saving functionality and integrated alarm monitoring in one versatile controller.